Application of HMC9000S+AIN16-C+AIN16-PT+HRM3300


About 30 nautical miles away from a costal port in the beautiful Zhanjiang city, Guangdong Province, there was a huge ship of nearly 10,000 tons sand pumping ship. The two 12-cyclinder water pump engines are controlled by HMC9000S, and the 12 cylinder temperatures of the engines are detected by the expanded analog input module AIN16-PT. The temperature of 8 shafts is detected by the expanded analog input module AIN16-C, and the shaft temperature signal is converted from PT100 to 4~20mA current type signal through the temperature transmitter to the AIN16-C. The AIN16-C then transmits it to the diesel engine controller HMC9000S through CANBUS (EXPANSION) communication, and finally displays the real-time temperature and protection of the shaft. HMC9000S transmits the engine information to the remote control module HRM3300 in cab through CANBUS (REMOTE) communication, and can also control engine start/stop remotely through HRM3300.


Project Control System Introduction


HMC9000S engine controller: can be widely used in marine emergency units, main propulsion units, DG units or water pump units. Its remote monitoring module interface enables remote monitoring, which can remotely control engine start, stop, etc.



HMC9000S



AIN16-PT Analog Input Module---16-way PT100 Sensor Input Module



AIN16-C Analog Input Module---16-way 4~20 mA Sensor Input Module



HRM3300 remote control module suits for the remote monitoring of HMC9000S engine controller



Typical Application of Marine Controller Communication



Site Pictures



Sand Pumping Ship



HRM3300 in Cab



Staff Operating HRM3300



Water Pump Engine



Water Pump Engine Cylinder Temperature



Water Pump Engine Main Shaft Temperature



PT100 to 4~20mA Temperature Transmitter



HMC9000S engine partial parameters



Common Fault Analysis:


1. HMC9000S and AIN16 communication failure:


Fault cause:

  • CAN H and CAN L of CANBUS (EXPANSION) communication are reversed;

  • CANBUS (EXPANSION) communication did not short circuit the CAN L and 120 Ω matching resistor on the controller;

  • If the distance of CANBUS (EXPANSION) communication line is too long, SGCAN300 relay conversion module (MSC or RS485 communication to optical fiber) should be added.


2. Inaccurate display of temperature or pressure sensor:


Fault cause:

  • Sensor curve setting is wrong;

  • Sensor is broken.


3. HMC9000S and HRM3300 communication failure:


Fault cause:

  • CAN H and CAN L of CANBUS (REMOTE) communication are reversed;

  • CANBUS (REMOTE) communication did not short circuit the CAN L and 120 Ω matching resistor on the controller;

  • If the distance of CANBUS (REMOTE) communication line is too long, SGCAN300 relay conversion module (MSC or RS485 communication to optical fiber) should be added.






1 次查看0 則留言
作家相片Zhengzhou SmartGen

2020 is destined to be an extraordinary year, there are too many unforgettable moments burned in our hearts;


The country's economic, social and livelihood development suffered a major setback in 2020 due to the impact of the coronavirus;


In 2020, all rural impoverished population under the current standard have been out of poverty;


In 2020, Chang'e 5 return capsule carries lunar samples back to the earth;


......


2020 is coming to an end. Let's review the experience accompanied by SmartGen.


2020 will soon pass, this year has left us too many special memories. Let's say goodbye to the extraordinary 2020 that we have experienced and persevered together, and let's welcome the new 2021 together!




1 次查看0 則留言
bottom of page